MELS for Split Type Air-Conditioners
Policy Details
COP (W/W) and Standby Power (W)
-
Single-split (non-inverter)
-
1 tick: NA
-
2 tick: COP100% ≥ 4.04
-
3 tick: 4.29 ≤ COP100% < 4.86 and Standby power ≤ 18
-
4 tick: COP100% ≥ 4.86 and Standby power ≤ 18
-
5 tick: COP100% ≥ 5.50 and Standby power ≤ 4
-
-
Multi-split (non-inverter)
-
1 tick: NA
-
2 tick: COP100% ≥ 4.04
-
3 tick: 4.29 ≤ COP100% < 4.86 and Standby power ≤ 9 x N
-
4 tick: COP100% ≥ 4.86 and Standby power ≤ 9 x N
-
5 tick: COP100% ≥ 5.50 and Standby power ≤ 7 x N
-
-
Single-split (inverter) (COP100, Weighted COP)
-
1 tick: NA
-
2 tick: Weighted COP ≥ 4.04 and COP100% ≥ 3.34
-
3 tick: Weighted COP ≥ 4.29, COP100% ≥ 3.78 and Standby power ≤ 18
-
4 tick: Weighted COP ≥ 4.86, COP100% ≥ 4.29 and Standby power ≤ 18
-
5 tick: Weighted COP ≥ 5.50, COP100% ≥ 4.86 and Standby power ≤ 4
-
-
Multi-split (inverter) (COP100, Weighted COP)
-
1 tick: NA
-
2 tick: Weighted COP ≥ 4.04 and COP100% ≥ 3.34
-
3 tick: Weighted COP ≥ 4.29, COP100% ≥ 3.78 and Standby power ≤ 9 x N
-
4 tick: Weighted COP ≥ 4.86, COP100% ≥ 4.29 Standby power ≤ 9 x N
-
5 tick: Weighted COP ≥ 5.50, COP100% ≥ 4.86 and Standby power ≤ 7 x N
-
COP100% is defined as the ratio of total cooling capacity to effective power input at full load cooling capacity
For split (inverter) type air-conditioners, the model shall meet both the minimum COP100% and weighted COP
Weighted COP = 0.4 x COP100% + 0.6 x COP50%
N is the number of indoor and outdoor units
Standby power is expressed in Watts